Load Characteristic Model: CMPLDWNF

 

Model Equations and/or Block Diagrams

-This represents a load model identical to the CMPLDW model, except that all the parameters related to the Distribution Equivalent have been removed (the first 17 parameters of CMPLDW and the MVABase).

Parameters:

FmA FmA: Motor A fraction of load P
FmB FmB: Motor B fraction of load P
FmC FmC: Motor C fraction of load P
FmD FmD: Motor D fraction of load P
Fel Fel: Electronic load fraction of load P
PFel PFel: Electronic load power factor
Vd1 Vd1: Voltage below which electronic load decreases, p.u.
Vd2 Vd2: Voltage below which electronic load is zero, p.u.
frcel frcel : Fraction of electronic load that recovers from low voltage trip
PFs PFs: Power factor of static load component
P1e P1e: Static load – exponent of first P term
P1c P1c: Static load – coefficient of first P term
P2e P2e: Static load – exponent of second P term
P2c P2c: Static load – coefficient of second P term
Pfrq Pfrq: Frequency sensitivity factor for P
Q1e Q1e: Static load – exponent of first Q term
Q1c Q1c: Static load – coefficient of first Q term
Q2e Q2e: Static load – exponent of second Q term
Q2c Q2c: Static load – coefficient of second Q term
Qfrq Qfrq: Frequency sensitivity factor for Q
Mtypa Mtypa: Motor A type
Mtypb Mtypb: Motor B type
Mtypc Mtypc: Motor C type
Mtypd Mtypd: Motor D type
LFma (Type 3) LFma: Motor loading factor, (Type 1) LFma: Motor loading factor
Rsa_CompPFa (Type 3) Rsa: Stator resistance, p.u., (Type 1) CompPFa: Power Factor
Lsa_Vstalla (Type 3) Lsa: Synchronous reactance, p.u., (Type 1) Vstalla: Stall voltage, p.u.
Lpa_Rstalla (Type 3) Lpa: Transient reactance, p.u., (Type 1) Rstalla: Stall resistance, p.u.
Lppa_Xstalla (Type 3) Lppa: Subtransient reactance, p.u., (Type 1) Xstalla: Stall reactance, p.u.
Tpoa_Tstalla (Type 3) Tpoa: Transient open circuit time constant, sec., (Type 1) Tstalla: Stall time delay, sec.
Tppoa_Frsta (Type 3) Tppoa: Subtransient open circuit time constant, sec., (Type 1) Frsta: Fraction of load that can restart after stalling
Ha_Vrsta (Type 3) Ha: Inertia constant, sec., (Type 1) Vrsta: Voltage at which restart can occur, p.u.
Etrqa_Trsta (Type 3) Etrqa: Mechanical torque exponent, (Type 1) Trsta: Restart time delay, sec.
Vtr1a_Fuvra (Type 3) Vtr1a: First low voltage trip level, p.u. V, (Type 1) Fuvra: Fraction of load with undervoltage relay protection
Ttr1a_Vtr1a (Type 3) Ttr1a: First low voltage trip delay time, sec., (Type 1) Vtr1a: First undervoltage trip level, p.u.
Ftr1a_TTr1a (Type 3) Ftr1a: First low voltage trip fraction, (Type 1) Ttr1a: First undervoltage trip delay time, sec.
Vrc1a_Vtr2a (Type 3) Vrc1a: First low voltage reconnection level, p.u. V, (Type 1) Vtr2a: Second undervoltage trip level, p.u.
Trc1a_Ttr2a (Type 3) Trc1a: First low voltage reconnection delay time, sec., (Type 1) Ttr2a: Second undervoltage trip delay time, sec.
Vtr2a_Vc1offa (Type 3) Vtr2a: Second low voltage trip level, p.u. V, (Type 1) Vc1offa: Contactor voltage at which tripping starts, p.u.
Ttr2a_Vc2offa (Type 3) Ttr2a: Second low voltage trip delay time, sec., (Type 1) Vc2offa: Contactor voltage at which tripping is complete, p.u.
Ftr2a_Vc1ona (Type 3) Ftr2a: Second low voltage trip fraction, (Type 1) Vc1ona: Contactor voltage at which reconnection is complete, p.u.
Vrc2a_Vc2ona (Type 3) Vrc2a: Second low voltage reconnection level, p.u. V, (Type 1) Vc2ona: Contactor voltage at which reconnection starts, p.u.
Trc2a_Ttha (Type 3) Trc2a: Second low voltage reconnection time delay, sec., (Type 1) Ttha: Thermal time constant, sec.
Th1ta (Type 1) Th1ta: Thermal protection trip start level, p.u. temperature
Th2ta (Type 1) Th2ta: Thermal protection trip completion level, p.u. temperature
Tva (Type 1) Tva: Voltage measurement lag, sec.
LFmb (Type 3) LFmb: Motor loading factor, (Type 1) LFmb: Motor loading factor
Rsb_CompPFb (Type 3) Rsb: Stator resistance, p.u., (Type 1) CompPFb: Power Factor
Lsb_Vstallb (Type 3) Lsb: Synchronous reactance, p.u., (Type 1) Vstallb: Stall voltage, p.u.
Lpb_Rstallb (Type 3) Lpb: Transient reactance, p.u., (Type 1) Rstallb: Stall resistance, p.u.
Lppb_Xstallb (Type 3) Lppb: Subtransient reactance, p.u., (Type 1) Xstallb: Stall reactance, p.u.
Tpob_Tstallb (Type 3) Tpob: Transient open circuit time constant, sec., (Type 1) Tstallb: Stall time delay, sec.
Tppob_Frstb (Type 3) Tppob: Subtransient open circuit time constant, sec., (Type 1) Frstb: Fraction of load that can restart after stalling
Hb_Vrstb (Type 3) Hb: Inertia constant, sec., (Type 1) Vrstb: Voltage at which restart can occur, p.u.
Etrqb_Trstb (Type 3) Etrqb: Mechanical torque exponent, (Type 1) Trstb: Restart time delay, sec.
Vtr1b_Fuvrb (Type 3) Vtr1b: First low voltage trip level, p.u. V, (Type 1) Fuvrb: Fraction of load with undervoltage relay protection
Ttr1b_Vtr1b (Type 3) Ttr1b: First low voltage trip delay time, sec., (Type 1) Vtr1b: First undervoltage trip level, p.u.
Ftr1b_TTr1b (Type 3) Ftr1b: First low voltage trip fraction, (Type 1) Ttr1b: First undervoltage trip delay time, sec.
Vrc1b_Vtr2b (Type 3) Vrc1b: First low voltage reconnection level, p.u. V, (Type 1) Vtr2b: Second undervoltage trip level, p.u.
Trc1b_Ttr2b (Type 3) Trc1b: First low voltage reconnection delay time, sec., (Type 1) Ttr2b: Second undervoltage trip delay time, sec.
Vtr2b_Vc1offb (Type 3) Vtr2b: Second low voltage trip level, p.u. V, (Type 1) Vc1offb: Contactor voltage at which tripping starts, p.u.
Ttr2b_Vc2offb (Type 3) Ttr2b: Second low voltage trip delay time, sec., (Type 1) Vc2offb: Contactor voltage at which tripping is complete, p.u.
Ftr2b_Vc1onb (Type 3) Ftr2b: Second low voltage trip fraction, (Type 1) Vc1onb: Contactor voltage at which reconnection is complete, p.u.
Vrc2b_Vc2onb (Type 3) Vrc2b: Second low voltage reconnection level, p.u. V, (Type 1) Vc2onb: Contactor voltage at which reconnection starts, p.u.
Trc2b_Tthb (Type 3) Trc2b: Second low voltage reconnection time delay, sec., (Type 1) Tthb: Thermal time constant, sec.
Th1tb (Type 1) Th1tb: Thermal protection trip start level, p.u. temperature
Th2tb (Type 1) Th2tb: Thermal protection trip completion level, p.u. temperature
Tvb (Type 1) Tvb: Voltage measurement lag, sec.
LFmc (Type 3) LFmc: Motor loading factor, (Type 1) LFmc: Motor loading factor
Rsc_CompPFc (Type 3) Rsc: Stator resistance, p.u., (Type 1) CompPFc: Power Factor
Lsc_Vstallc (Type 3) Lsc: Synchronous reactance, p.u., (Type 1) Vstallc: Stall voltage, p.u.
Lpc_Rstallc (Type 3) Lpc: Transient reactance, p.u., (Type 1) Rstallc: Stall resistance, p.u.
Lppc_Xstallc (Type 3) Lppc: Subtransient reactance, p.u., (Type 1) Xstallc: Stall reactance, p.u.
Tpoc_Tstallc (Type 3) Tpoc: Transient open circuit time constant, sec., (Type 1) Tstallc: Stall time delay, sec.
Tppoc_Frstc (Type 3) Tppoc: Subtransient open circuit time constant, sec., (Type 1) Frstc: Fraction of load that can restart after stalling
Hc_Vrstc (Type 3) Hc: Inertia constant, sec., (Type 1) Vrstc: Voltage at which restart can occur, p.u.
Etrqc_Trstc (Type 3) Etrqc: Mechanical torque exponent, (Type 1) Trstc: Restart time delay, sec.
Vtr1c_Fuvrc (Type 3) Vtr1c: First low voltage trip level, p.u. V, (Type 1) Fuvrc: Fraction of load with undervoltage relay protection
Ttr1c_Vtr1c (Type 3) Ttr1c: First low voltage trip delay time, sec., (Type 1) Vtr1c: First undervoltage trip level, p.u.
Ftr1c_TTr1c (Type 3) Ftr1c: First low voltage trip fraction, (Type 1) Ttr1c: First undervoltage trip delay time, sec.
Vrc1c_Vtr2c (Type 3) Vrc1c: First low voltage reconnection level, p.u. V, (Type 1) Vtr2c: Second undervoltage trip level, p.u.
Trc1c_Ttr2c (Type 3) Trc1c: First low voltage reconnection delay time, sec., (Type 1) Ttr2c: Second undervoltage trip delay time, sec.
Vtr2c_Vc1offc (Type 3) Vtr2c: Second low voltage trip level, p.u. V, (Type 1) Vc1offc: Contactor voltage at which tripping starts, p.u.
Ttr2c_Vc2offc (Type 3) Ttr2c: Second low voltage trip delay time, sec., (Type 1) Vc2offc: Contactor voltage at which tripping is complete, p.u.
Ftr2c_Vc1onc (Type 3) Ftr2c: Second low voltage trip fraction, (Type 1) Vc1onc: Contactor voltage at which reconnection is complete, p.u.
Vrc2c_Vc2onc (Type 3) Vrc2c: Second low voltage reconnection level, p.u. V, (Type 1) Vc2onc: Contactor voltage at which reconnection starts, p.u.
Trc2c_Tthc (Type 3) Trc2c: Second low voltage reconnection time delay, sec., (Type 1) Tthc: Thermal time constant, sec.
Th1tc (Type 1) Th1tc: Thermal protection trip start level, p.u. temperature
Th2tc (Type 1) Th2tc: Thermal protection trip completion level, p.u. temperature
Tvc (Type 1) Tvc: Voltage measurement lag, sec.
LFmd (Type 3) LFmd: Motor loading factor, (Type 1) LFmd: Motor loading factor
Rsd_CompPFd (Type 3) Rsd: Stator resistance, p.u., (Type 1) CompPFd: Power Factor
Lsd_Vstalld (Type 3) Lsd: Synchronous reactance, p.u., (Type 1) Vstalld: Stall voltage, p.u.
Lpd_Rstalld (Type 3) Lpd: Transient reactance, p.u., (Type 1) Rstalld: Stall resistance, p.u.
Lppd_Xstalld (Type 3) Lppd: Subtransient reactance, p.u., (Type 1) Xstalld: Stall reactance, p.u.
Tpod_Tstalld (Type 3) Tpod: Transient open circuit time constant, sec., (Type 1) Tstalld: Stall time delay, sec.
Tppod_Frstd (Type 3) Tppod: Subtransient open circuit time constant, sec., (Type 1) Frstd: Fraction of load that can restart after stalling
Hd_Vrstd (Type 3) Hd: Inertia constant, sec., (Type 1) Vrstd: Voltage at which restart can occur, p.u.
Etrqd_Trstd (Type 3) Etrqd: Mechanical torque exponent, (Type 1) Trstd: Restart time delay, sec.
Vtr1d_Fuvrd (Type 3) Vtr1d: First low voltage trip level, p.u. V, (Type 1) Fuvrd: Fraction of load with undervoltage relay protection
Ttr1d_Vtr1d (Type 3) Ttr1d: First low voltage trip delay time, sec., (Type 1) Vtr1d: First undervoltage trip level, p.u.
Ftr1d_TTr1d (Type 3) Ftr1d: First low voltage trip fraction, (Type 1) Ttr1d: First undervoltage trip delay time, sec.
Vrc1d_Vtr2d (Type 3) Vrc1d: First low voltage reconnection level, p.u. V, (Type 1) Vtr2d: Second undervoltage trip level, p.u.
Trc1d_Ttr2d (Type 3) Trc1d: First low voltage reconnection delay time, sec., (Type 1) Ttr2d: Second undervoltage trip delay time, sec.
Vtr2d_Vc1offd (Type 3) Vtr2d: Second low voltage trip level, p.u. V, (Type 1) Vc1offd: Contactor voltage at which tripping starts, p.u.
Ttr2d_Vc2offd (Type 3) Ttr2d: Second low voltage trip delay time, sec., (Type 1) Vc2offd: Contactor voltage at which tripping is complete, p.u.
Ftr2d_Vc1ond (Type 3) Ftr2d: Second low voltage trip fraction, (Type 1) Vc1ond: Contactor voltage at which reconnection is complete, p.u.
Vrc2d_Vc2ond (Type 3) Vrc2d: Second low voltage reconnection level, p.u. V, (Type 1) Vc2ond: Contactor voltage at which reconnection starts, p.u.
Trc2d_Tthd (Type 3) Trc2d: Second low voltage reconnection time delay, sec., (Type 1) Tthd: Thermal time constant, sec.
Th1td (Type 1) Th1td: Thermal protection trip start level, p.u. temperature
Th2td (Type 1) Th2td: Thermal protection trip completion level, p.u. temperature
Tvd (Type 1) Tvd: Voltage measurement lag, sec.